The CorelixRF CRF-PA-400M440M-100W is a GaN solid-state RF power amplifier for 400–440 MHz communication test benches. Its overview lists 100 W rated CW output; the electrical table separately gives 80 W minimum and 100 W typical saturated output power. Integrating this module means matching the DC supply, external heat sink, RF path and host controls to the selected configuration and operating point.
Define the power required at the load
Use 400–440 MHz as the RF operating window. Choose measurement points that represent the frequencies the bench will actually use, including any points where cable, filter or fixture loss is greatest. The output required at a DUT or load must account for the loss between that reference plane and the amplifier output.
The source electrical conditions are a 50 Ω system, +28 V DC nominal supply and CW operation at normal temperature unless an entry states otherwise. Keep those conditions with the 100 W rated CW description and the separate 80 W minimum / 100 W typical Psat entries. Neither entry supplies an EVM, ACPR or linear-modulated output limit.
For a modulated communication signal, specify bandwidth, peak-to-average behavior, required output and distortion at the chosen measurement plane. The listed gain is 46 dB minimum, 48 dB typical and 50 dB maximum; it does not establish the input level for every large-signal operating point. Confirm the maximum permitted input and the appropriate drive curve before setting the source.

Keep operating current separate from the protection threshold
The operating-voltage range is +24 to +32 V, with +28 V nominal. The current entries are 16 A typical and 20 A maximum. A separate protection description states over-current lock above 22 A. Use the operating-current values to review the supply and harness, then agree how the bench current limit coordinates with the module protection. The 22 A threshold is not a recommended continuous current.
At 28 V and the listed 16 A typical current, V × I gives 448 W of DC input. That arithmetic is a planning check, not a measured heat load or a guarantee of current at every RF level. Determine the installed thermal load from the actual electrical and RF operating point; subtracting an unrelated output reading from a typical input figure would give a misleading heat estimate.
Check voltage at the amplifier terminals under the intended load, rather than relying on the power-supply display alone. Include harness voltage drop, connector current handling, grounding, startup behavior and the agreed current limit in the bench design. The separate over-voltage lock above 32 V is a fault condition, not extra operating headroom.
Design the heat-sink installation around the operating point
The source lists a 160 × 120 × 25 mm module, 1.4 kg weight and external heat-sink cooling. Reserve the mounting surface, thermal interface, RF connector access and control-harness space together. A module outline does not supply the heat sink’s thermal resistance, contact pressure or airflow requirement.
The listed operating-temperature range is −40 to +60 °C. It is distinct from a case, baseplate or junction-temperature limit, and the source does not provide a quantitative thermal derating curve. Describe the bench ambient, enclosure, mounting stack, RF duty profile and operating time when the cooling arrangement is reviewed.
Over-temperature shutdown and recovery are listed, but numerical trip and recovery temperatures are not provided in these files. Establish the permitted operating and alarm conditions for the delivered configuration. A protection function should support fault handling while the heat sink carries the intended operating load.
Choose the source version before wiring the controller
The M version is described without an internal VCO, while V includes an internal VCO source and 10 Hz frequency-stepping information. An externally driven communication bench needs the appropriate M input path. The V frequency/bandwidth adjustment field is a separate control description; it does not extend the stated 400–440 MHz RF operating band.
The electrical table names SMA-KFD46 RF input/output interfaces. The connector reference explicitly identifies RF IN for M. It lists D-Sub 15-Pin Female for control and “Pull-core Capacitance” for the power entry. Confirm the selected version’s drawing and pinout before assigning a cable or power connection; do not route the DC supply through a control pin merely because the table groups control and power in one row.
The source gives 20 dB gain-adjustment range and 0.5 dB step information. M1 options include gain adjustment, RS485 monitoring/control, forward/reverse power indication, temperature output and alarm reset where applicable. Identify the included options, command protocol and gain state at startup in the quotation. Forward/reverse indicators are listed as 0–3 V signals; using them as a power measurement requires the relevant transfer function and calibration.
The PA enable/disable time is listed as 100 µs maximum. That value describes the named control timing; it does not establish source settling time, a complete RF switching sequence or arbitrary pulse capability. Coordinate the host command, RF source and fault state for the intended bench rather than treating one timing number as the whole sequence.

Make RF and fault readings refer to the same configuration
Record source frequency, input level at the amplifier, gain command, output measurement plane, load, supply voltage/current and thermal conditions together. For a directional-coupler sample, apply the appropriate coupling factor and sample-path loss once. An instrument reading at the sample port is not automatically the power delivered at RF OUT or at the DUT.
The M-version entries include 20 dB maximum noise figure, 1.5 maximum input VSWR and −60 dBc typical spurious. Second and third harmonics are listed at −10 dBc typical. Preserve the parameter and typical/maximum definitions, then agree the frequency, output level, measurement bandwidth and fixture conditions for any project limit. The input VSWR value does not state the allowed output-load mismatch.
Over-VSWR locked shutdown is listed alongside over-temperature, over-voltage and over-current protection. Obtain the delivered unit’s alarm mapping, reset behavior and permitted protection-check method before planning a fault test. Keep a configuration-specific test record distinct from the catalog specification; these source files do not provide a measured acceptance result for the bench being built. A related configuration review is 400-440 MHz 150W UHF RF Power Amplifier Protection FMEA. Keep its ratings, interfaces and installation conditions distinct when comparing it with this setup.
Compare a different platform when the requirement moves
This 100 W configuration addresses a fixed 400–440 MHz bench with its own supply, external cooling and control requirements. If the load-power requirement exceeds its available margin after path loss and any waveform back-off, the 400–440 MHz 200 W integration guide provides a separate higher-power case. Review that model’s dimensions, current and protection values before changing the bench design. Use the narrowband RF amplifier platforms page to compare the product family, then request the exact configuration and evidence required by this review.
For a wider operating band or another integration format, use the RF amplifier platform directory to identify a candidate before requesting its exact-model data. A larger power label does not establish a compatible harness, heat sink or alarm protocol.
Discuss the configuration for your communication bench
Send the 400–440 MHz operating points, required power at the load, waveform, available drive, M/M1/V preference, supply/current-limit arrangement, heat-sink installation, connectors and control requirements. Include the measurements and documentation needed for the intended bench so CorelixRF can review the exact configuration.