Start a CW-versus-pulse decision by describing the signal at the RF input and the state of the amplifier bias. A pulsed RF amplifier may receive a pulsed RF signal while its bias remains on, or it may use a defined bias-gating sequence. These cases have different timing, current and off-state behavior. The application name alone does not identify the required mode.

Write each operating case separately

Case Describe explicitly Ask the supplier to confirm
Continuous RF drive Level, modulation, run duration and load Continuous capability and thermal/linearity conditions
Pulsed RF with continuous bias RF pulse format and inter-pulse input behavior Envelope fidelity, off-state output and average electrical demand
RF pulse with switched bias or enable RF-to-control timing, levels and sequence Turn-on settling, turn-off behavior and permitted sequence
Several modes on one unit All cases and transitions between them Supported combinations and mode-specific restrictions

CW means continuous wave; a CW capability statement still needs frequency, power definition, supply, cooling and load conditions. Modulated operation may add linearity requirements. A radar evaluation can use different waveforms, and a communication test can include bursts. Specify the actual waveform rather than choosing hardware from those labels.

Separate RF average power from heat load

For identical rectangular RF pulses with approximately constant on-state power and negligible off-state output, duty cycle D = pulse width × PRF and average RF power Pavg ≈ Pon × D. Use consistent time units. A waveform with droop, significant edges, bursts or off-state power needs an average over the defined interval; its instantaneous peak is not automatically the level to multiply by duty cycle.

This RF calculation does not determine DC input power, idle dissipation, switching losses or cooling capacity. Those depend on the amplifier and operating case. Low duty cycle also does not authorize a higher peak input or output than the supplier permits. Ask for the permitted drive envelope and the relevant thermal conditions.

Do not extend a pulsed specification into CW service

The June 2026 V1.0 CRF-PA-1000M2000M-1500W source illustrates the distinction. It covers 1,000–2,000 MHz and places 1500 W Output Power in the minimum column, while pulse width 1–50 µs and duty cycle 5% appear in the typical column. This is a pulsed configuration reference, not evidence of continuous operation at that output.

The source lists 62 dB minimum gain, a 20 dB maximum gain-control range, N-Female input/output, RS485/LAN, AC 220 V ±10% at 50/60 Hz and an air-cooled 5U rack format. Its mechanical model includes the suffix -P. Retain that configuration distinction when requesting a drawing or quotation, and ask for separate supported conditions if continuous operation is required.

Choose evidence for the mode being requested

For continuous operation, agree the output definition, duration and thermal observations. For pulsed operation, add pulse-top, edge, settling and off-state definitions, the complete timing sequence and the supported waveform combinations. A nominal control interface does not establish its timing response. The RF measurement guide helps organize the power and thermal records.

Compare the relevant pulsed RF amplifier platforms only after the cases are written. If one unit must handle several modes, include the transition sequence and state which limits apply in each mode.

Send CorelixRF your drive-and-bias operating cases, including waveform, load, timing, supply and cooling conditions, for configuration review.