The CorelixRF CRF-PA-2900M3500M-25000W and CRF-PA-2000M4000M-5000W answer different S-band pulse requirements. The first lists a 25 kW peak output reference over 2.9–3.5 GHz; the second lists 5 kW pulsed output over 2–4 GHz. Compare the frequency and pulse conditions before comparing the headline powers.
Read the two configurations side by side
| Entry | CRF-PA-2900M3500M-25000W | CRF-PA-2000M4000M-5000W |
|---|---|---|
| Frequency | 2,900–3,500 MHz | 2,000–4,000 MHz |
| Minimum output entry | 25 kW rated peak | 5,000 W pulsed |
| Typical pulse entries | 200 μs; 20% duty | 1–50 μs; 5% duty |
| RF input / output | N-Female / WR284 | N-Female / 7/16-Female |
| Cooling | Water cooling | Forced-air cooling |
| Control / pulse interface | RS485/LAN; no pulse connector defined in this datasheet | RS485/LAN; SMA-F pulse interface listed |
The pulse entries appear in the typical column of the respective electrical tables. They provide comparison references, not complete guaranteed timing envelopes. Confirm the required width, repetition pattern, duty, modulation, burst duration and run time for the selected model. Both electrical tables use a 50 Ω system, rated AC supply and the standard production test configuration; the 25 kW table explicitly identifies pulsed operation. Both list AC 380 V ±10% at 50/60 Hz; their different cooling methods still require separate installation designs. For a separate configuration example of this engineering question, see 2–4 GHz 5000 W Pulsed Amplifier: Facility Power, Load and Cooling; its frequency, power and interface conditions belong to that example.
The 2.9–3.5 GHz span lies inside 2–4 GHz, but the reverse is not true. For example, a requirement at 3.8 GHz is outside the listed 25 kW band. A larger peak-power number does not extend that band. At a shared frequency, pulse and output requirements still need separate review rather than an assumption that the larger platform can reproduce every smaller-platform pulse.

Compare pulse energy and average RF output
For a periodic rectangular pulse with constant RF power during the pulse and negligible RF power between pulses, duty cycle equals pulse width multiplied by PRF. Pulse energy equals pulse power multiplied by width; average RF output equals pulse power multiplied by duty cycle. The following calculations assume those conditions and use the listed reference numbers. They are not measurements or additional guaranteed operating points.
| Assumed reference | Derived PRF | RF energy per pulse | Average RF output |
|---|---|---|---|
| 25 kW, 200 μs, 20% duty | 0.20 / 0.0002 = 1,000 Hz | 25,000 × 0.0002 = 5 J | 25,000 × 0.20 = 5,000 W |
| 5 kW, 50 μs, 5% duty | 0.05 / 0.00005 = 1,000 Hz | 5,000 × 0.00005 = 0.25 J | 5,000 × 0.05 = 250 W |
The same calculated PRF accompanies different pulse energies and average RF outputs. PRF alone therefore cannot describe the required stimulus. Average RF output is also not the amplifier’s waste heat. Supply demand, efficiency and internal losses require their own data; neither 5,000 W nor 250 W should be copied into a chiller requirement.

Compare the RF path and control evidence by model
WR284 and 7/16-Female lead to different mating assemblies, support needs and measurement arrangements. Waveguide routing, couplers, loads, adapters, and antennas must be rated for the pulse power and duty profile. Keep the calibration plane and any path correction with the result instead of assuming mechanical connection proves RF suitability.
The 5 kW datasheet lists an SMA-F pulse interface; it does not provide a trigger voltage, polarity or timing specification in that entry. The 25 kW datasheet does not identify a pulse-control connector. Do not transfer one model’s connector to the other. Engineers should ask for the final control protocol during project review.
Protection descriptions differ as well. The 25 kW document lists over-temperature, over-drive and VSWR protection with alarms. The 5 kW protection section lists alarm/fault functions, temperature/current monitoring and alarms, with optional RF detection. It does not establish the same shutdown guarantees. Match alarm behavior and supplied monitoring to the selected model.
Use the comparison to narrow the request
Use the pulsed RF amplifier platforms when neither reference matches. Send the required frequencies, pulse shape and width, PRF, duty, peak/average output definition, load interface and run duration. Request the supporting timing, output and cooling data for the exact configuration being proposed.